GST-G1223 16eA 1U ATS with 2 x C20 Inputs, Local Digital Powermeter, 8 x IEC C13 and 2 x IEC C19
Outlets
Geist General style unit - actual item may look slightly different
Description:
GEIST 16A 1U ATS with 2 x C20 Inputs, Local Digital Powermeter, 8 x IEC C13 and 2 x IEC C19 Outlets Transfer Switch - ATRCN102-102I82ST6 - 19" horizontal, 20 amp 208V auto transfer switching, ten receptacles (8 C-13 & 2 C-19) on the rear, two LEDs power-on indicators (one per power source available), NO circuit breaker, NO on/off switch, Digital Power Meter, this meter features a 4-digit display that cycles through 4 critical power measurements (Power Factor, Amps, Volts, and Watts) and two power cords (6-20P). Power Feeds A and B must be Phase Synchronized
Features:
General pic guide G1221- actual item may look slightly different
Specification:
Quantity Of Inputs 2 (Dual Input)
Voltage 208
Amperage 20
VA per Input 3.3kW
Frequency 50/60 Hz
Over Current Protection None
Switch Auto Switching - event of power failure
Indicators - LED(s) 2
Power Cable Wire Gauge 12/3
Power Cable Length 10'
Plug Type
Click to View (2) NEMA 6-20P
Combined Total Receptacle/Socket Quantity 10
Receptacle/Socket Type
Click to View IEC C-13
Quantity on Rear 8
Style Banks of 4
Maximum Output per Receptacle/Socket 15A per receptacle bank
Voltage per Receptacle/Socket 208
Receptacle/Socket Type
Click to View IEC C-19
Quantity on Rear 2
Style Individual
Maximum Output per Receptacle/Socket 20A
Voltage per Receptacle/Socket 208
Auto Switching Relay Yes ****
Heavy Steel - Black Powder Coat Yes
Made in the USA Yes
Configuration 19" Horizontal Rackmount
Flush Mount Optional
23" Recess Mount (use with 19" unit) Optional
Panel Mount Brackets Optional
Adjustable Mount Brackets Yes
Product Warranty Three Year
Certification/Agency Approvals UL & c-UL Listed 60950
Certification/Agency Approvals RoHS Compliant
Chassis Dimensions (HxWxD) 1.72" x 17.1" x 8.5"
Unit Weight 9 lbs.
****Switching Type - DPDT Relay
UL Relay Rating - 35 Amps @ 277 VAC
Expected Life @ Rated Load - 100,000 Operations
Mechanical Life - 10,000,000 Operations
Operate Time - <25 Milliseconds
Release Time - <25 Milliseconds
Pick Up - 85% or less of Nominal
Power Feeds A and B must be Phase Synchronized
* PLEASE NOTE: SWITCH OVER SPEEDS OF MORE THAN 15ms MAY NOT BE SUITABLE FOR ALL SERVERS. Always check your computers exact requirements.