KWX-ATS32A8x2H3 PDUeX Auto Transfer Switch 2 x Inputs 32A IND309 to 8xC13 + 2xC19 Lockable Switching Outlets, Surge Protected and High speed (8-12 ms Switching ) 32 Amp Feed Monitored KWX-N3 Range

KWX ATS 2C19+8C13port Output ports

Description:

KWX Rack mount Automatic Transfer Switch (KWX ATS) 32A IND309 to 8xC13 + 2xC19 Lockable Outlets Allows remote port switching Monitors the Bar level power consumption, delivers consistent power, to single-corded equipment. The KWX ATS has dual input power cords supplying power to the connected load. In the event where the primary power source becomes unavailable, the KWX ATS will flawlessly source power from the secondary source without interrupting critical loads. The KWX ATS has built-in network connectivity, which allows for remote management via Web, SNMP or Telnet/SSH interfaces, and provides sensors recognition, ability to cascade up to 4 units, power factor recognition, 10 lockable IEC C13, dry connection. Optional: temperature and humidity, smoke alarm, water logging alarm, infrared alarm, and door open alarm. Monitor: monitor the total current, monitor the total KwH, monitor the input voltage, monitor environment temperature, monitor environment humidity, monitor environment smoke. Monitor water logging, infrared monitoring, and door open monitoring. Alarm settings: total current over the limit, on the temperature limit, on the humidity limit, smoke alarm, and water logging alarm, infrared enters alarm, door open alarm.

Features:

-2 x 32 Amp IND 309 Commando Input to 10 x Oulets Locking 8xC13 + 2x C19 Outlets

- BAR LEVEL Monitoring

- Port Switching

- High Speed - Fast switching A-B Source 8~12 ms

-Surge Protected

- Alarm Settings

- Sensor Port for enviromental sensors ( optional extra )

- RS232 Port

- Current monitor Outlets Metering

- 32 Amp Feed.


Locking Sockets view

Specification:

NO.1 Customer PDUeX Part number KWX-ATS32A8x2H3
1. Item Description
2. Product series KWX-N-ATS-1
3. Product Size W x D x H= 19“ x 206.9 x 44.45 mm
4. Mounting length 465 mm
5. Case color Black
6. Socket type
8 x Lockable IEC 320 C13 10 A
2 x Lockable IEC 320 C19 16 A
Two Input
A&B
IEC60309 32A
Cable: 3×6.0mm2×2m


7. LED display
Input/output voltage
Total load current
Power supply A or B line operating state
8. Function
Automatic switch over power A and power B
Overload alarm
When over the 16A threshold the ATS alarm will buzz and the
LED display will flash.
Switching time (From "A" to "B" line): 8 ms ≤ 12 ms

Function Illustration Parameter Note

Working voltage Normal working AC90~250V
Working band Under normal working 47~60Hz
Access port
Serial port Via Serial port monitor access RS485 port
Sensor port Sensors access RS485 port
Secondary development RS485 Customized protocol
Software upgrade Software on circuit Support software upgrade on the circuit of
hardware
Monitor
Monitor the input voltage
Resolution:1V
Accuracy: ±1%+1 digit
Meter range: 90~350V
Monitor the total current
Resolution: 0.1A
Accuracy: ±1%+1 digit
Meter range: 0.1~40A
Monitor the total kwh Resolution: 0.1KW·H
Accuracy: 1 grade
Monitor Environment
Temperature
Resolution: 1℃
Accuracy: ±1%+1 digit
Meter range: -30~100℃
Optional
Monitor Environment Humidity
Resolution: 1%
Accuracy: ±1%+1 digit
Meter range: 01~99%
Optional

KWX ATS Specification
3
Monitor Environment Smoke Max: 25 ㎡ available Optional
Monitor water logging Water logging or drop monitor Optional
Infrared monitoring The max monitor distance: 16m Optional
Door open monitor Min. 5mm open distance available Optional
Surge protection failure monitor ATS still normal working when failure Optional
Alarm limit setting
Total current limit
Auto identify limit rationality
Temperature limit
Humidity limit
Outlets alarm
Total current over limit alarm
KWX-S/ KWX-N series local alarm ways: ATS
buzzer alarm, sound and light alarm, Dry connect;
KWX-N series remote alarm: E-mail, SMS,
SNMP TRAP, WEB page notice, TELNET/SSH
notice
Temperature over limit alarm Optional
Humidity over limit alarm Optional
Smoke Alarm Optional
Water logging alarm Optional
Infrared enter alarm
KWX-N series remote alarm: E-mail, SMS,
SNMP TRAP, WEB page notice, TELNET/SSH
notice
Optional
Door open alarm Optional
Surge protection failure alarm Optional
Display, Indicate
Outlets indicators Each outlets with a indicator Optional
6 digital indicators Nixie tube show the current/voltage, inquiry
products information, Alarm information;
Manu button operation
Inquiry information Inquiry product information, Alarm information,
current etc.
On/off Alarm sound, Dry
connect
Close/ open alarm sound and dry connect output,
Dry connect have normal open/off two choice,
passive, touch spot can connect 2A 250VAC
Protection
Surge protection
Difference mode:±2kV
Common mode :±2KV
flux: 3KA
The max discharge current: 5KA
Optional
Each way with fuse
Breaking capacity : 1500A;
Protect main line break, facility, power line
suffering, Fuse range: 0.1~16A
Optional
Circuit Breaker protection Breaking capacity : 6000A Optional
Recoverable overload protector Overload protection Optional
Management clock synchronization Regulate ATS system clock
Intelligent recognition
Outlets recognition Automatic read the sockets type and numbers
Sensors recognition Sensors port no need be defined, Automatic read
the sensors type and numbers
The MAX output current and
ATS power
Help user to limit facilities connect number and
type
Power factor recognition
Help user to know the current consuming
apparatus
Sensors in 1 ~ 8pcs same or different
sensors connect in one ATS
Flexible sensor input, extend and choose,
Customized for new sensors Optional
Cascade chain KWX-N with KWX-S Cascade Directly connection via net cable, 4 sets Cascade
at most


compatible products

£995.74 £1,194.89 (Inc vat)

Qty: