EN2326 - Enlogic Bar Metered & Oultlet Switched 16A 0U Vertical PDU, 24 outlets, 20x C13, 4x C19 (2000 Series) EN2.0, 1PH, IEC 60309 316P6, 230V, 3.68kVA
Description:
The EN2326 Input Metered, Outlet Switched PDU combines energy metering, power and environmental monitoring with remote outlet on/off switching to monitor, protect, and manage the rack environment. Utility grade metering at the phase input and internal circuit breaker levels provides comprehensive overload monitoring. Outlet power-up sequencing protects against inrush current overload and allows users to define equipment boot-up order and timing. While remote on/off control allows authorised users to power-cycle remote equipment and implement rack-level power access controls to power on/off each outlet. Advanced network management features allow for remote access and integration with accessories including environmental monitoring and security access solutions.
Features:
• Network Connectivity - Dual ports: 1x Gigabit Ethernet (10/100/1000 Mbps) and 1x (10/100 Mbps)
• Ethernet Cascading - Up to 64 units share a single “daisy-chain” Ethernet IP address
• DC Power Sharing - Each PDU can provide DC power sufficient to power network management electronics and sensors in a neighbouring PDU in the event of AC power source loss
• Dual Ethernet Support - Dual Ethernet ports for redundant communication
• Dual Network Access - Dual network connectivity allows redundancy and Multiple stockholder connectivity for up to 64 units in Ethernet cascading mode
• Remote Connectivity - HTTP(s), iPV4 and iPV6, SSH, Virtual Serial, SNMP (v1, v2c, v3), JSON-RPC, LDAP(S), FTP/SFTP, RADIUS, Redfish DMTF RESTful API
• WebUI Interfacce - Data efficient REACT framework with native mobile device support
Supply feed connector IEC 60309
Specification:
EN2326 - Enlogic Bar Metered & Oultlet Switched 16A 0U Vertical PDU, 24 outlets, 20x C13, 4x C19 (2000 Series) EN2.0, 1PH, IEC 60309 316P6, 230V, 3.68kVA
Metering & Switching
Metering Attributes Voltage(V),Current(A),Apparent Power(kVA),Real Power(kW),Power Factor, Energy(kWH)
Metering Accuracy ± 1% to ISO/IES 62052-21
Metering Location Input Phase and circuit breaker measurements
Remote Outlet Switching yes
Electrical
Electrical Input
Acceptable input voltage 200-240VAC, 1ph
Input current (phase) 16A
Input frequency 50/60 Hz
Max Input power 3.84 kVA @ 240 VAC
Input Plug IEC 60309 316P6
Electrical Output
Output voltage 230VAC
Maximum output current (phase) 16A
Overload protection (internal) No internal circuit breakers
Outlet configuration (20)C13, (4)C19
Physical
Chassis Dimensions (L x W x D) in 58.66 x 2.05 x 2.09
Depth at circuit breaker, in NA
Input cord length 10'
Environmental
Operating Temperature -5 to 60°C (23 to 140°F)
Storage Temperature -20 to 60°C (-4 to 140°F)
Humidity (operating/storage) 5-90% RH / 5-95% RH; non-condensing
Max operating elevation, above MSL 3,000 m (9,840 ft)
Compliance
Safety verification CE, Demko Certified to IEC/EN60950-1
Environmental ROHS, REACH
* BTO - 2 Week Manufacturing Lead Time *