3313390 Rittal 20 Kw Liquid Cooling Package LCP Inline Cooling DX, LCP Inline DX/FC - SK LCP Inline DX, 20kW, 300x2000x1200
Description:
Liquid Cooling Package LCP Inline DX, LCP Inline DX/FC - SK LCP Inline DX, 20kW, 300x2000x1200 380-480V, 3~, 50/60Hz
Features:
Benefits
Maximum energy efficiency due to EC fan technology and IT-based control
Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
Temperature monitoring and control
With redundant temperature sensor integrated at the air end as standard
Thanks to the speed-regulated compressor, the cooling output is ideally adapted to actual requirements
Specific maintenance of the LCP DX due to separation of cooling and server racks
Applications
Ideal for IT cooling of small and medium-sized locations
One or two racks can be cooled separately
Function principle
The LCP is designed for siting within a bayed enclosure suite. Hot air is drawn in from the aisle at the rear of the device, cooled by the high-capacity compact impellers, and blown back into the room or cold aisle after cooling.
Absorbed thermal energy is emitted to the ambient air at the external condenser location, without heating up the installation room
RITTAL INLINE COOLING UNIT
pm-elk
Specification:
Material
Sheet steel, spray-finished
Colour
RAL 7035
Options
Humidifier
Dehumidification and reheater
Condensate drain pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Design
Suite cooling
Monitoring
Direct connection of the unit via SNMP over Ethernet
Integration into RiZone
Note
Variant with UL approval available on request
Total cooling output to DIN EN 14511
Useful cooling output L22 L35: 20 kW
Total cooling output
20
Total cooling output/Number of fan modules
20 kW/4
Modulation range
5 ‐ 20 kW
Air throughput (unimpeded air flow)
At 50 Hz: 4,800 m³/h
Dimensions
Width: 300 mm
Height: 2,000 mm
Depth: 1,200 mm
To fit enclosure type
VX IT
Installation in bayed enclosure suite
Flush
Rated operating voltage
380 V - 480 V, 3~, 50 Hz/60 Hz
Rated current max.
At 50 Hz: 12.4 A
Max. cooling output
20 kW
Type of electrical connection
Connection clamp
Duty cycle
100 %
Cooling medium
Refrigerant
EC fan
Yes
SNMP card
Yes
Fans may be exchanged with the system operational
Yes
Temperature control
Linear fan control
Inverter-controlled compressor
Pre-fuse
Miniature circuit-breaker/fuse: 32 A
Operating temperature range
-20 °C...50 °C
Noise level
At 50 Hz: 68 dB(A)
Protection category to IEC 60 529
IP 20
Options
Humidifier
Dehumidification and reheater
Condensate drain pump
Low-temperature/high-temperature condenser (-40 °C/+53 °C)
Packs of
1 pc(s).
Net weight
255 kg
Gross weight
266 kg
Customs tariff number
84186900
EAN
4028177953826
ETIM 9
EC002515
ETIM 8
EC002515
ECLASS 8.0
27180712
Product description
LCP Inline DX, 20 kW, flush, RAL 7035, WHD: 300 x 2000 x 1200 mm, 380 – 480 V/3~/50 – 60 Hz