PX4-5538-E8 Raritan 400V,16A 3-Phase (L-N), 11.1kVA, (12) C13, (12) Cx PDU
Description:
Inlet metered + outlet Metered + switched Power Distribution Unit, 230/400V Wye 16A IEC 60309 3P+N+PE 6Hr, 11.1 kvA, Bottom/Angled input, 24 outlets: 12x C13, 12x combined C13/C19 outlets, FEATURES: Billing-Grade (± 0.5%) Energy and Power Quality Metering [kW, kVA, V, A, Voltage and Current Harmonic Distortion, True and Displacement Power Factor, Voltage Dip and Voltage Swell, Neutral Current and Voltage, Current Inrush, and Crest Factor]. Remote network monitoring via HTML, JSON-RPC, Redfish API, SSH, Telnet, MODBUS/TCP, and SNMPv3. Hot-swappable Controller with onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM. Physically cascade 32 PDUs under one Ethernet port or 16 PDUs with USB. Linking (Shared GUI) of up to 8 PDUs. Environmental monitoring [temp/humidity] capable – up to 32 sensor functions or 12 sensor packages. Individual outlet numbers labeled on chassis. Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives. Data logging via HTTP/S or MQTT. Wi-Fi Capable. USB Webcam Capable. iOS or Android App. Dual 10/100/1000 Ethernet port. Mechanical locking function for Outlets. 16A Breakers, 10kAIC. Breaker metering and alarming (0V detection). Maximum ambient temperature 60°C at full load. Attested passed VAPT (Vulnerability Assessment and Penetration Testing), IPv6 Ready, ISO 27001 compliant. Vendor: Raritan; Part Number: PX4-5538-E8
Features:
Energy Metering
Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy
Class 0.5 meter
Metering per input line
Yes
Metering per Branch Circuit Breaker
Yes
Metering per Output Receptacle
Yes
Remote Outlet Switching
Yes
Power Quality Monitoring
Voltage and Current Harmonic Distortion; Distortion Power Factor; Voltage Dip and Voltage Swell; Neutral Current, Current Inrush, Crest Factor
Outlet Power Distribution
Alternating Branch
Replaceable Controller
Yes, hot-swappable
Environmental Sensor Ready
Yes
Compatible Sensors
Temperature, Humidity, Air Flow, Differential Pressure, Dust/Particle, Water Leak, Proximity/Motion, Vibration, Dry Contact, and Contact Closure.
View all sensors.
PDU Linking
Link up to 8 PDUs where the Primary PDU has knowledge and power information from the attached Expansion PDUs. Redundant power from the first expansion unit ensures uptime even if the Primary PDU loses power.
Cascading
Physically cascade 32 PDUs under one ethernet port or 16 PDUs with USB using bridging mode, or additionally, save IP addresses using a single IP address with port forwarding.
Linking
Yes, a maximum of 8 PDUs can be linked using the PDU Link Port; PDU 1 is defined as the Primary PDU and can link up to 7 additional PDUs, called Link PDUs, totaling 8 PDUs.
Networking
(10/100/1000 Base T) Ethernet, Secondary redundant (10/100/1000 Base T) Ethernet. Optional WiFi (802.11 a/b/g/n).
Remote Management
HTTP(s); SSH (CLI); Telnet; RS-232 (Serial); SNMP version v2/v3; SMTP; JSON-RPC API; MODBUS-TCP; Redfish API
Onboard Display
Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet); Alarms; Configuration information (name, ratings, IP / Networking information). Auto-flip orientation.
Specification:
Input
Input Plug 230/400V Wye 16A IEC 60309 3P+N+PE 6Hr
Nominal Voltage 400V
Maximum Input Current 16A
Rated Input Current 16A
Power Capacity 11.1kVA
Cord Length 10ft/3m
Output
Receptacles (Output Connections) (12) C13, (12) Cx
Overload Protection 0
Physical
Dimensions (WxDxH) 56mm x 65mm x 1298mm
Unit Weight 11 lbs
Shipping Weight 16.25 lbs
Shipping Dimensions (HxDxW)
1459 x 255 x 125 mm
Mounting G4-HOLDER-FOR-ZU
Environmental
Operating Temperature/Environment 60 C
Operating Relative Humidity 85%
Operating Elevation 0-10000ft
Conformance
Regulatory Approvals
CE
Warranty
Standard 2 years manufacturer warranty